FREE SHIPPING OPTION FOR LOWER 48 States!!!

FBC System Compatible Logo

USDA Biopreferred logo

nsf logo

NFPA logo

Click Links Below For:

pdf logoIceClear FS MSDS

pdf logoIceClear FS Technical Data Sheet

pdf logoNSF Letter

EXTENDED LIFE Wet Fire System Antifreeze / Winterizer

 

TYPICAL PROPERTIES

 

US Patents
One or more claims 5,876,621; 5,980,774; 6,506,318; 6,890,451; 7,270,768 and issued and pending continuations thereof.

HMIS 1 0 0 0

IceClear® FS

iceclear fs logo
Wet Fire System 48% Glycerin Antifreeze / Winterizer With Inhibitor

IceClear HD glycerin antifreeze / coolant / heat transfer fluidDESCRIPTION
IceClear FS is a patented 48% factory pre-mixed of highly refined USP glycerin per NFPA guidelines, designed for use in all types of wet fire systems, including CPVC.

IceClear FS is FBC™ System Compatible. FBC™ System Compatible indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold®, BlazeMaster® and Corzan® pipe and fittings. FBC™, FlowGuard Gold®, BlazeMaste®r and Corzan® are licensed trademarks of The Lubrizol Corporation.

IceClear FS meets the requirements of ASTM D2809, ASTM 4340, ASTM 1384, and ASTM D2570. Our state-of-the-art, non-nitrated corrosion package, provides outstanding extended protection against corrosion of steel, copper, brass, solder, cast aluminum, and cast iron. IceClear FS lubricates pumps and valves, provides excellent scaling resistance, is fully compatible with gaskets, seals, elastomers and other non-metallic pump and equipment parts, offers a freeze point of -15 F.

Don't need a corrosion inhibitor?
Please see BioTherm Fluids Fire 48, a chemically pure 48% USP glycerin mix for fire systems.

Safety / Environment

USDA Biopreferred logoIceClear FS is the leader in quality, safety and environmental concerns. FS is a certified USDA Biobased Product with a biobased content of 98% as tested by ASTM D6866 through the USDA BioPreferred® Program.

nsf logoIceClear® FS is NSF listed HT2. IceClear FS is readily biodegradable, non-toxic and non-hazardous. IceClear FS combines highly refined and/or food-grade glycerin and an industry proven premier corrosion inhibitor package which does not include old technology such as nitrites, molybdates or phosphates. Glycerin is considered "GRAS", (Generally Recognized As Safe) by the FDA (Federal Food and Drug Administration).

Applications

Designed for wet industrial fire systems and environmentally sensitive anti-freeze / heat transfer applications, IceClear FS can be used in virtually all static and low temperature applications such as:

OUTSTANDING BENEFITS AND FEATURES:


Testingrefractometer

specific gravity testerIceClear® FS is a glycerin based product, DO NOT use testers designed for glycols. Freeze point range can quickly be determined by a special tester (pictured left) available from Orison or more accurately by a refractometer (Brix refractometer pictured right) to be used with our conversion chart for glycerin.

IceClear® FS adheres to particle surfaces and clings to equipment surfaces with little run-off and settling. This prevents freezing, clumping and sticking, and keeps product moving freely.

How Much Does My System Require?

IceClear Pipe Volume Table
 
Pipe Diameter
 
1/2"
3/4"
1"
1 1/2"
2"
2 1/2"
3"
3 1/2"
4"
Gallons/100' Copper Tubing (Type L)
1.2
2.5
4.3
9.3
16.1
24.8
35.4
47.8
62.0
Gallons/100' Steel Pipe
1.6
2.8
4.5
10.5
17.5
25.0
39.0
53.0
66.7

The chart below is supplied as a guide for diagnostic / maintenance purposes. The values are calculated values and are only approximations. Note: Diluting this product more than 8% with water may be subject to bacterial contamination.

IceClear FS % /Specific Gravity
Glycerin %
Brix Value (Refractometer)
Freeze Point F/C
ViscositycSt @68F (20C)
100 / 1.139
48
42
-15/-26
10.8
75 / 1.10
36
32.7
2/-16.5
7.9
50 / 1.07
24
23
16/-9
5.5

MAINTENANCE DIRECTIONS
1. Follow original equipment manufacturer’s instructions for adding antifreeze.
2. Test fluid prior to filling system.
3. Evacuate all water/fluid from system and drain drops per NFPA requirements.
4. Can be used with glycerin only based technology. Do not mix with other non-glycerin anti-freeze/heat transfer fluids or chemicals.
5. Follow NFPA guidelines for testing the fluid after filling. Samples should be taken from a minimum of a high point and low point. Results should be comparable to each other and to
the sample of the fluid tested prior to filling system.
6. NFPA requires a tag to be affixed to the riser indicating the date tested or replaced, the type and concentration by volume of fluid used, system capacity (in volume), contractor name and license number and a statement indicating if the entire system was drained and replaced with antifreeze.

The use of IceClear FS should be in conformance with any/all state, local and NFPA requirements. NFPA 25 requires the freeze point of the system should be tested at least once/year to confirm proper concentration and freeze point of the fluid.

FREE Shipping option to lower 48 states!*

credit cards picturepaypal logoGSA Advantage Logo

RE-SELLER DISCOUNTS AVAILABLE

Please call Lane at 800.460.2403 for distributor pricing

SPECIAL INTERNET PRICING!
5 Gallon
ICFS-5
$89.00
Quantity:
55 Gallon
ICFS-55
$591.25
Quantity:
275 Gallon
ICFS-275
$2612.50
Quantity:
       
Freeze Point Tester
ICT4
$19.95
Quantity:
Hanna Refractometer
HI96801
$189.95
Quantity:

Note: Glycerin concentrations less than 40% may be subject to bacterial contamination.

Also available in 330 gallon totes and bulk. Please call 800.460.2403 for larger sizes.

*Does not include lift gate for freight deliveries.


link to home page link to Orison links page link to products page link to contact page link to Orison search page